Insulation monitor RN 5897/274

The insulation monitor RN 5897/274 of the VARIMETER IMD family is a solution for optimal insulation monitoring of modern IT systems. The device can be used in the most flexible way for AC, DC and AC/DC systems. The setting of the parameters and the switching values is done by simple and operator friendly rotational switches on front of the device. The operating status is indicated user friendly via a multicolour LED. With a sealable transparent cover the device is protected against manipulation. The RN5897/274 has a semiconductor output (PWM) to indicate the insulation resistance.

Advantages and Features:

  • Insulation monitoring according to IEC/EN 61557-8
  • Universal application in non-earthed AC, DC, AC/DC networks up to AC max. 250 V or DC max. 300 V
  • With connection facility of an external coupling device RL 5898 for voltages up to AC 400 V / DC 500 V or RP 5898 for voltages up to AC 690 V / DC 1000 V
  • Extended operating temperature range of – 40 … + 70 °C
  • Optimised insulation resistance monitoring also during mains voltage variation
  • Self-test every full operating hours
  • Detection of symmetric and asymmetric insulation faults
  • Universal application in non-earthed AC, DC, AC/DC networks
  • Easy adjustment of response value and setting parameter via rotational switch
  • Suitable for large leakage capacitances up to 150 μF
  • Monitoring also with voltage-free mains
  • Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
  • Protective conductor PE1/PE2 with broken wire detection (can’t be switched off)
  • Setting range of 2nd response value (alarm): 1 … 500
  • 1 changeover contacts each for insulation failures alarm and device failures
  • Energized or de-energized on trip can be selected for indicator relay
  • With multicolour status LED to indicate the state of operation.
  • Automatic and manual device self-test
  • Alarm storage selectable
  • Protection against manipulation by sealable transparent cover
  • External control input for combined test- / reset-button with additional stop of the measuring function
  • With semiconductor output to indicate the insulation resistance (PWM)
  • 3 wide voltage input for auxiliary voltage
  • Width 52.5 mm