Insulation monitor RN 5893/100

The insulation monitor RN 5893/100 of the VARIMETER IMD family is a solution for optimal insulation monitoring of modern IT systems. The device can be used in the most flexible way for AC, DC and AC/DC systems. Mains areas of applications are non-earthed DC charging stations for electric vehicles with mains voltages up to DC 1000 V that need an extended temperature range. The setting of the parameters and the switching values is done via Modbus. All measured values, device statuses and parameters can also be read out via Modbus. All functions of the device can also be operated via Modbus. The operating status is indicated user friendly via a multicolour LED. With a sealable transparent cover the device is protected against manipulation.

Advantages and Features:

  • Insulation monitoring according to IEC/EN 61557-8
  • Suitable for DC charging stations for electric vehicles acc. to IEC/EN 61851-23:2014/AC:2016-06
  • Universal application in non-earthed AC, DC, AC/DC networks up to AC max. 250 V or DC max. 300 V
  • Connection of an external coupling device RP 5898 for voltages up to AC 690 V / DC 1000 V possible
  • Extended operating temperature range of – 40 … + 70 °C
  • Very fast reaction time ≤ 1 s
  • Optimised insulation resistance monitoring also during mains voltage variation
  • Detection of symmetric and asymmetric insulation faults
  • Easy adjustment of response values and setting via Modbus RTU-interface
  • Suitable for large leakage capacitances up to 5 μF
  • Monitoring also with voltage-free mains
  • Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
  • Protective conductor PE1/PE2 with broken wire detection (can’t be switched off)
  • 2 parameterizable changeover contacts (for insulation fault pre-alarm, insulation fault-alarm, insulation fault-alarm on DC+/DC- or device fault) each galvanic separated
  • With galvanic separated Modbus RTU interface
  • 2 separate adjustable response thresholds (using e.g. for pre-alarm and Alarm)
  • Setting range of 1st response value (Pre-alarm): 1 … 500
  • Setting range of 2nd response value (alarm): 1 … 500
  • Energized or de-energized on trip can be selected for indicator relay
  • With multicolour status LED to indicate the state of operation.
  • Automatic and manual device self-test
  • Alarm storage selectable
  • Protection against manipulation by sealable transparent cover
  • External control input for combined test- / reset-button with additional stop of the measuring function
  • 2 wide voltage input for auxiliary voltage
  • Width 52.5 mm