Insulation monitor RN 5897/011

The insulation monitor RN 5897/011 of the VARIMETER IMD family is a solution for optimal insulation monitoring of modern IT systems. The device can be used in the most flexible way for AC, DC and AC/DC systems even with large leakage capacity to earth (PE). The adjustment of the setting values is simple and user friendly done on 2 rotary switches on the front of the device. Via display and LEDs the measured value, device parameters and device status are indicated easy to read. With a sealable transparent cover the device is protected against manipulation. The RN 5987/011 has an additonal Modbus RTU-interface. All measured values, device states and parameters can be read out, set and parameterized. All functions available on the device can also be operated via Modbus.

Advantages and Features:​

  • Insulation monitoring according to IEC/EN 61557-8​
  • Detection of symmetric and asymmetric insulation faults​
  • Quick fault localisation through selective earth fault detection to L+ and L-​
  • Universal application in non-earthed AC, DC, AC/DC networks up to 300 V​
  • With connection facility of an external coupling device:​
  • RL 5898 for voltages up to AC 400 V / DC 500 V​
  • RP 5898 for voltages up to AC 690 V / DC 1000 V​
  • RR 5898 for voltages up to AC 1000 V / DC 1500 V​
  • Easy adjustment of response values and setting parameter via rotational switch and menu display or via Modbus RTU-interface​
  • Suitable for large leakage capacitances up to 1000 μF​
  • Optimised reaction time for large leakage capacitances​
  • Monitoring also with voltage-free mains​
  • Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)​
  • Protective conductor PE1/PE2 with broken wire detection (can’t be switched off)​
  • 2 changeover contacts each for insulation failures-Pre-alarm and –alarm each galvanically isolated​
  • With galvanic separated Modbus RTU interface​
  • Trigger output for insulation fault locating system​
  • 2 separate adjustable response thresholds (using e.g. for pre-Alarm and Alarm)​
  • Setting range of 1st response value (Pre-Alarm): 1 kΩ … 2 MΩ​
  • Setting range of 2nd response value (Alarm): 1 kΩ … 2 MΩ​
  • 2 changeover contacts for insulation failures –Pre-Alarm and –Alarm​
  • Energized or de-energized on trip can be selected for indicator relay​
  • Display for indication of measured value, device parameters and device status​
  • Setting the maximum leakage capacitance to shorten the response time​
  • Automatic and manual device self-test​
  • Alarm storage selectable​
  • Protection against manipulation by sealable transparent cover​
  • External control input for combined Test-/Reset-button​
  • 2 wide voltage input for auxiliary voltage​
  • Width 52.5 mm